The transfer that flooded the wash room
Two levels, actuator feedback, a coasting motor and a latched trip.
Repair a complete transfer controller. Open the route before pumping, stop at the receiving target, and protect the source.
Every Pro challenge is free for a day when it comes round as the daily challenge.
Pro challengeOpen before pumping; coast before closing
Test 1 of 7ResetInputONStartInputOFFLevelReceiving tank80 %StateTransfer phase0- Level
- Hard · 40 points
- Kind
- Find the fault
- Time
- About 45 min
- Pass rate
- New
- Machine
- 3D two-tank transfer rig
- Siemens
- SCL
- Rockwell
- Structured Text
- Beckhoff
- Structured Text
The motor started while the valve was still moving. A full receiver overflowed. Restoring permission restarted a transfer without another press.
What the checks test
- Open feedback gates the pump; a missing signal gets a fresh 500 ms timeout.
- Stop at 80%, keep the route open while the motor coasts, then close it.
- Dry source, lost permission and faults a trip; recovery needs a fresh Start.
The checks run 7 tests on the machine, scan by scan: Open before pumping; coast before closing; Dry-source priority beats completion and Reset; Open feedback timeout boundary; Lost feedback removes pump immediately and times a fresh wait; Held Start cannot restart on restored permission; Stop and physical failure are immediate; Cannot begin with no room or no water.
Where you’d find this
A factory wash tank is refilled from a bigger storage tank. The valve must be open before the transfer pump starts.
A pump that runs with no water can ruin its seal. Overfilling the wash tank spills water onto the floor.
How it should behave
- Start and phase
- State 0 is idle. A fresh Start with Permit, no Fault/PumpDamaged, SourceLevel > 10% and Level < 80% enters 10. ValveCmd opens the route; PumpOn stays OFF until ValveOpen enters 20. Process one phase transition per scan.
- Feedback timeout
- In 10 or 20, missing ValveOpen continuously for 500 ms trips to 90. The first enabled Delay invocation starts at zero. Returning feedback resets the wait. In 20, PumpOn must turn OFF immediately whenever ValveOpen is FALSE.
- Full receiver and coast
- Level >= 80% enters 30: PumpOn OFF, ValveCmd still ON. Wait for MotorSpeed <= 0 rpm before 50, closing ValveCmd and setting Done. DrainValve remains OFF throughout. Ordinary entry commands may lag State by one scan; entry to 30 removes PumpOn immediately.
- Trip and recovery
- In active states, lost Permit, Fault, PumpDamaged or SourceLevel <= 10% wins over completion and immediately enters 90: Alarm ON, PumpOn/ValveCmd/Done OFF. Stop returns to 0 unless already tripped. Reset clears 50/90 only with Start released, Permit, no Fault/PumpDamaged and SourceLevel > 10%. Restoration cannot restart without a fresh Start.
- Physical evidence
- SourceLevel measures a 400 L tank; Level measures a 100 L receiver. FlowRate is actual transfer. PumpWear and SpilledLitres show consequences. Dry or blocked pumping accumulates illustrative wear; full wear stops the shaft. These are teaching effects, not real damage predictions or safe limits.
Run and briefly press Start. Watch the source fall and receiver rise. Select the transfer valve to compare command and travel. Set ValveStuck before a fresh run to test the opening timeout.
More challenges
- The soak that never really happenedTemperature memory, a continuous soak and separate coolant flow.Hard · Find the fault
- E-stop wins, every timeStop at once, stay stopped, reset on purpose.Easy · Make it safe
- A broken wire must stop itNormally closed stop and overload contacts, the safe way round.Easy · Make it safe
- Close the guard, stay stoppedOpening the guard stops the belt. Closing it does not start it.Easy · Make it safe