Trip, reset, restart on purpose
Handle a drive fault without a surprise restart.
P-101’s drive trips if the pump is overloaded. Start latches DriveRun and Stop wins. A drive fault (DriveFault) turns DriveRun OFF at once and cancels the run request. FaultLamp shows DriveFault. Send DriveReset while FaultReset is held, but only while DriveRun is OFF. After a reset, the pump stays OFF until someone presses Start again.
Pro missionTrip, clear the cause, reset, then restart on purpose
Test 1 of 5OverloadOverload (cause)OFFDriveRunRun commandONFaultLampFault lampOFFDriveResetReset to driveOFF- Level
- Advanced
- Time
- About 25 min
- Reward
- +300 XP
- Rig
- 3D pump skid
- Siemens editors
- SCL, LAD, FBD, GRAPH
- Rockwell editors
- Structured Text, Ladder, FBD, SFC
- Course stage
- 25. Trip, reset, restart on purpose
What the tests check
- A trip turns DriveRun OFF at once. Start does nothing while the drive is faulted.
- DriveReset follows FaultReset only while DriveRun is OFF. A press with the cause still there clears nothing.
- After a reset, the pump stays OFF until a new Start.
- Try it Use the buttons below the model and watch the rig respond.
- Test solution Every check runs on your code in one press.
- Replay If one fails, step through it one scan at a time to see why.
Where you’d see this on site
A pump's drive trips on overload. A fitter clears the blockage, and the operator resets the drive from the panel.
A reset that restarts the pump can injure the person who just fixed it. The pump must wait for a deliberate Start.
In a block of flats, a basement tank holds water from the mains. Two pumps push it up to the taps above. One runs while the other waits as a spare. A low-water switch stops the pumps before the tank runs dry.
- Street mainsWater enters the building
- Storage tankHolds a supply for the pumps
- Water pumpsPush water to the floors aboveYou are here
- Taps upstairsResidents use the water they need
On a real site: places, parts and safety
- Block of flats — pushing water up to the top floors
- Brewery — sending hot water to a brewing tank
- Water-treatment works — moving water between filter tanks
- Office building — pumping water round the heating pipes
A low-water switch can take away permission to run. The pump must stop before it runs dry and damages its seal.
The PLC can say ON even when a pump has failed. Check the measured flow as well as the command.
The Stop input in these exercises is not an emergency stop. Real machines also need guards, emergency stops and a safe way to cut the power.
The sizes, timings and cutaways are teaching choices, not a drawing of any one real installation.
Next in the course
- Keep the workshop in airRun a compressor between two pressures.Applied · 15 min · +250 XP
- One car at a timeRaise the arm for a ticket, lower it once the car is clear.Applied · 20 min · +300 XP
- Stop before the palletOpen and close a door that reverses for obstructions.Applied · 20 min · +300 XP
- Take turns, survive the stormAlternate two pumps and bring in the standby.Applied · 25 min · +300 XP