Empty until a fifth full
The level reads 0% while the tank fills. Find out why.
Find and fix the . LevelRaw is 0 counts at 4 mA (empty) and 27648 at 20 mA (full). LevelPV must read 0–100% in proportion, with decimals, and stay within 0–100%.
Pro missionOperator report: a fifth full reads 0%
Test 1 of 5LevelRawRaw input27648 countsLevelPVLevel shown100 %- Level
- Applied
- Time
- About 12 min
- Reward
- +200 XP
- Rig
- 3D process tank
- Siemens editors
- SCL, LAD, FBD
- Rockwell editors
- Structured Text, Ladder, FBD
- Course stage
- 21. Read a real transmitter
We refilled TK-101 after a clean. The sight glass showed about a fifth full, but LT-101 on the screen still said 0%. Then it caught up, and it reads 100% when the tank is full. The transmitter was calibrated last week.
What the tests check
- About a fifth full, 5530 counts, reads 20%.
- Half full, 13824 counts, reads 50%. Empty and full still read 0% and 100%.
- Readings a little outside the range stay at 0% or 100%.
- Try it Use the buttons below the model and watch the rig respond.
- Test solution Every check runs on your code in one press.
- Replay If one fails, step through it one scan at a time to see why.
Where you’d see this on site
After a tank clean, the sight glass shows it a fifth full while the screen still says empty. Both ends of the scale look right.
A scaling range that doesn't match the input card hides the bottom of the tank. Low-level alarms and pump protection then act on the wrong number.
At a drinks factory, valves let measured amounts of water and syrup into a mixing tank. An electric mixer blends them into one batch. An outlet valve then sends the drink to a holding tank. Filling machines bottle it from there.
- Ingredient tanksHold the water and syrup
- Mixing tankFill, mix and measure one batchYou are here
- Holding tankKeeps the finished drink ready
- Bottle fillerPuts the drink into bottles
On a real site: places, parts and safety
- Drinks factory — blending water and syrup
- Paint factory — mixing ingredients into a consistent colour
- Water-treatment works — preparing a measured chemical mixture
- Brewery — heating water for washing equipment
A full tank does not close its own inlet. Water keeps arriving until the valve closes, so an open inlet can flood the room.
A heater that is not covered by liquid can overheat. Real tanks have separate safety devices as well as the PLC programme.
The sizes, timings and cutaways are teaching choices, not a drawing of any one real installation.
Next in the course
- Catch a broken wireSpot a failed transmitter and stop trusting its number.Applied · 20 min · +300 XP
- Alarm limits that don’t chatterHigh and low level alarms with a deadband.Applied · 15 min · +250 XP
- Run a pump on a driveSend a run command and a speed, then wait for the drive to prove it.Applied · 20 min · +300 XP
- Trip, reset, restart on purposeHandle a drive fault without a surprise restart.Advanced · 25 min · +300 XP