Grey is normal
Save colour for the things an operator must act on.
Fix the compressor's operator screen so normal running looks calm and grey, and only a real problem shows in colour. Then make the flag low pressure and a motor that won't run, with no false alarms.
Pro missionA normal cut-in raises no flag
Test 1 of 4StartStart pushbutton: put the station into serviceOFFPressureReceiver pressure8MotorRunningInputONCompressorRunOutputOFF- Level
- Applied
- Time
- About 20 min
- Reward
- +300 XP
- Rig
- 3D air compressor station
- Siemens editors
- Ladder (LAD), SCL
- Rockwell editors
- Ladder, Structured Text
- Beckhoff editors
- Structured Text
- Course stage
- 36. Operator screens 1: grey is normal
What the tests check
- Normal running and stopped equipment look calm and grey, not green and red.
- Low pressure stands out with an alarm marker beside the value, showing its priority.
- LowPressure is in service below 5.0 bar, and clears at 5.5 bar or above.
- Out of service, LowPressure stays however low the pressure falls.
- MotorFault is TRUE only after CompressorRun has been ON for 2 s with MotorRunning OFF.
- The station control still works: CompressorRun cuts in below 6.0 bar.
- Try it Use the buttons below the model and watch the rig respond.
- Test solution Every check runs on your code in one press.
- Replay If one fails, step through it one scan at a time to see why.
Where you’d see this on site
A factory's compressor house is often watched from a screen in the maintenance office, one screen among a dozen.
If every screen is green and red all day, nobody spots the one compressor that has tripped until the air tools stop.
Almost every workshop and factory has a compressor like this in a back room. It feeds air tools, spray guns and the pneumatic cylinders on machines. The PLC starts the motor when the pressure falls to a lower limit and stops it at an upper limit, so the motor rests between charges.
- Air intakeFiltered room air
- CompressorSqueezes the air
- ReceiverStores it under pressureYou are here
- WorkshopAir tools and machines
On a real site: places, parts and safety
- Vehicle workshops and body shops
- Packaging and assembly lines with pneumatic cylinders
- Joinery shops and small factories
Isolate and vent the receiver before working on the pipework: stored air is stored energy.
Never adjust or block a safety valve to stop it lifting.
The sizes, timings and cutaways are teaching choices, not a drawing of any one real installation.
Next in the course
- Read it at a glanceAnswer 'is it all right?' in one second, in plain words.Applied · 25 min · +300 XP
- Alarms in priority orderNew alarms flash and sound until acknowledged; the urgent one comes first.Advanced · 30 min · +350 XP
- Ask before you can't undoConfirm only what can't be taken back, and say what will happen.Advanced · 30 min · +350 XP
- Same button, same placeFaceplates that work the same way every time, and say why not.Applied · 25 min · +300 XP