Challenge 12 · Find the fault · Pro

Which fault actually happened first?

A feedback timeout, first-out capture and a stuck Ack button.

Keep the first cause in TripCode while shutting PumpOn and ValveCmd immediately on a trip. Alarm stays ; Horn responds to a fresh Ack press.

This challenge is part of ProTry the full course, every mission and the expert challenges free for 7 days. No card needed.

Every Pro challenge is free for a day when it comes round as the daily challenge.

The 3D process tank this challenge runs on Pro challenge
Test replay

A healthy plant cannot reset while Start is still held

Test 1 of 7
Set by the testChecked by the testStep 6 of 6 · 480 ms
Level
Hard · 40 points
Kind
Find the fault
Time
About 40 min
Pass rate
New
Machine
3D process tank
Siemens
SCL
Rockwell
Structured Text
Beckhoff
Structured Text
The operator’s report · process tank
It first said valve timeout. Later it said motor fault. Acknowledging appeared to clear everything, then the plant started again.
Automatic checks

What the checks test

  1. TripCode captures the first cause and does not change before a valid Reset.
  2. Opening feedback gets 500 ms; an interrupted command starts a fresh wait.
  3. A held Ack cannot silence a later event. Alarm, Horn, PumpOn and ValveCmd are checked every .

The checks run 7 tests on the machine, scan by scan: A healthy plant cannot reset while Start is still held; First cause survives later faults; defined simultaneous priority; High-level boundary and held Ack cannot silence the next event; Feedback at the last allowed scan prevents a timeout; 500 ms timeout trips, latches and refuses unsafe reset; Interrupted travel gets a fresh timeout; Permission return never restarts a held Start.

On site

Where you’d find this

A brewery tank stops filling after an alarm. The engineer needs to know which fault came first, before later faults bury it.

If later faults overwrite the first fault code, the engineer goes to the wrong equipment. Using Ack to clear the alarm could restart equipment that is still faulty.

The machine

How it should behave

Start and flow
A fresh Start edge latches ValveCmd with Permit, no Stop and no Alarm. PumpOn is TRUE only with ValveCmd AND ValveOpen. Stop/Permit loss immediately removes both commands; restoration needs a new Start press.
Three causes
TripCode 0 = clear; 1 = Fault; 2 = Level >= 95%; 3 = ValveCmd without ValveOpen continuously for 500 ms. Call Delay every scan; its first true invocation starts at zero. The next invocation at 500 ms trips. Interrupted travel resets the delay.
First cause and priority
If more than one cause appears on the same scan, Fault wins, then high Level, then valve timeout. After capture, preserve TripCode even if another cause appears. Alarm = TripCode <> 0. Both process commands must be OFF on the trip scan.
Horn and Ack
A new capture sounds Horn. A rising edge of Ack silences only Horn. Holding Ack through a valid reset cannot silence the next new fault. Release and press it again.
Reset
Reset clears TripCode, Alarm and Horn only with Start released, Fault FALSE, Level < 95% and ValveStuck FALSE. The valve remains closed and a fresh Start is needed. Reset during an active cause cannot clear it.

Reset the simulation and select ValveStuck before pressing Run and Start. Watch ValveCmd and ValveOpen disagree while the valve stays shut. Test and replay the exact timeout boundary. Use Inputs to hold Ack while clearing and retriggering a fault; a new event must still sound Horn.