One scan too late
The pump command outlives a trip by one scan.
In Auto (Run ON), PumpOn runs the pump while it is healthy: no Fault, and Permit ON. A Fault or a lost Permit must turn PumpOn OFF on the very it happens. Find why it is one scan late and fix it.
Every Pro challenge is free for a day when it comes round as the daily challenge.
Pro challengeOperator report: the trip scan
Test 1 of 3RunInputONFaultInputONPermitInputONPumpOnPump commandOFF- Level
- Medium · 20 points
- Kind
- Find the fault
- Time
- About 10 min
- Pass rate
- New
- Machine
- 3D pump skid
- Siemens
- LAD and SCL
- Rockwell
- Ladder and Structured Text
- Beckhoff
- Structured Text
Every time the motor trips, the drive logs “run command present during trip”. The trend shows PumpOn still ON for one scan after the trip. Same thing when the outlet valve closes.
What the checks test
- Run turns PumpOn ON while there is no Fault and Permit is ON.
- A Fault turns PumpOn OFF on the same scan.
- Losing Permit turns PumpOn OFF on the same scan.
- Turning Run OFF stops the pump.
The checks run 3 tests on the machine, scan by scan: Operator report: the trip scan; Losing Permit stops it on the same scan; Run starts and stops it.
Where you’d find this
A pump on a variable speed drive that logs every run command it receives during a trip.
Drives and safety relays react within milliseconds. A command that lingers one scan after a trip can fault the drive or upset a safety function.
How it should behave
- Run
- Auto selected: run while healthy.
- Healthy
- No Fault, and Permit ON.
Pause, switch Run ON and step a few scans. Then switch Fault ON and press Step scan once: PumpOn must already be OFF.
More challenges
- The spare that keeps stealing the runAlternation, break-before-make and a failed recovery — together.Hard · Find the fault
- Which fault actually happened first?A feedback timeout, first-out capture and a stuck Ack button.Hard · Find the fault
- The bottle that was counted twiceRecover the right phase without counting a half-filled bottle.Hard · Find the fault
- The transfer that flooded the wash roomTwo levels, actuator feedback, a coasting motor and a latched trip.Hard · Find the fault