Challenge 07 · Find the fault · Free

The timer that never finishes

A three-second start delay that only works if you hold the button.

Pump P-101 should start 3 seconds after a press of Start, so the outlet valve has time to open first. Fix the delay so a short press is enough. Stop cancels a start that is still waiting, and stops a running pump.

Free, with no sign-up. Sign in to score the points and keep your streak.

The 3D pump skid this challenge runs on
Test replay

Operator report: a short press of Start

Test 1 of 3
Set by the testChecked by the testStep 5 of 5 · 3.7 s
Level
Easy · 10 points
Kind
Find the fault
Time
About 8 min
Pass rate
New
Machine
3D pump skid
Siemens
LAD and SCL
Rockwell
Ladder and Structured Text
Beckhoff
Structured Text
The operator’s report · pump skid
I press Start and nothing happens. If I hold Start for a full three seconds the pump starts, but it stops the moment I let go.
Automatic checks

What the checks test

  1. A short press of Start starts the pump 3 s later.
  2. PumpOn stays OFF during those 3 s.
  3. Stop cancels a start that is still waiting.
  4. Stop turns a running pump OFF.

The checks run 3 tests on the machine, scan by scan: Operator report: a short press of Start; Stop cancels a waiting start; Stop stops a running pump.

On site

Where you’d find this

A pump on a cooling loop waits a few seconds after Start, so its outlet valve can open first.

A timer fed straight from a push button never finishes. The pump either never starts, or runs only for whoever holds the button.

The machine

How it should behave

Start
A press starts the pump 3 s later.
Stop
Cancels a waiting start; stops a running pump.

Press Run, then click Start once. Watch the timer count to 3 s, then the pump starts.